] Y branch pipe
* For more information, refer accessory installation manual.
[Unit:mm(inch)]
Note:
If the large capacity indoor units are installed, below Y branch pipe should be used
NOTE
!
Use the Valve Group Control when 2 branches are connected with only 1 indoor unit which has higher
capacity than 61 kBTU.
Valve Group
SW01D
Setting
Valve Group
SW01D
Setting
Not control 0 No. 5,6/7,8 Valve Control 8
No. 1,2 Valve Control 1 No. 1,2/5,6 Valve Control 9
No. 2,3 Valve Control 2 No. 1,2/7,8 Valve Control A
No. 3,4 Valve Control 3 No. 3,4/5,6 Valve Control B
No. 5,6 Valve Control 4 No. 3,4/7,8 Valve Control C
No. 6,7 Valve Control 5 No. 1,2/3,4/5,6 Valve Control D
No. 7,8 Valve Control 6 No. 1,2/3,4/6,7 Valve Control E
No. 1,2/3,4 Valve Control 7 No. 1,2/3,4/7,8 Valve Control F
2. Main function of SW01D
* Master Only