Tips for Attaching the Pipe In / Pipe Out Thermistors
• Put the thermistor cable in a separate protective tube.
• Always add a pull-relief to the thermistor cable to avoid strain on
the thermistor cable and loosening of the thermistor. Strain on the
thermistor cable or loosening of the thermistor can result in bad
contact with the pipe and incorrect temperature measurement.
Water
Attaching the Pipe Thermistors
Thermistor Installation
AHU COMMUNICATIONS KIT INSTALLATION
Figure 13: Attach Pipe Thermistors.
• To avoid water accumulating on the thermistor tip, position
the thermistor cable slightly below the thermistor tip, or
install the thermistor tip parallel with the cable.
Do not include a 90° angle or a kink in the thermistor
cable, nor install the thermistor tip upside down.
Figure 14: Thermistor and Cable Installation.
1. Securely attach the thermistor to the pipe with a field-supplied pipe strap.
2. Insulate the thermistor with a field-supplied insulation sheet that is >5t.
Thermistors must be securely attached with a pipe strap� The equipment will
not operate properly if thermistors are not making good physical contact in the
appropriate installation location�
Step 2
Figure 15: Positioning the Thermistor Cable and Tip.
2
Tie wrap
Thermistor
45°
1