44
PAHCMR000 AHU Communication Kit Installation Manual
Due to our policy of continuous product innovation, some specications may change without notication.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
Error Code Description Details
CH01 Return Air (Room) Thermistor Error
Return air (room) thermistor has disconnected from AHU, or
has short circuited.
CH02 Pipe In Thermistor Error
Pipe in thermistor has disconnected from AHU, or has short
circuited.
CH03
Communication Error Between Wired Remote Controller and AHU
Communications Kit
No communication signal for more than three (3) minutes
from the controller to the AHU Communications Kit.
CH05
Communication Error Between
AHU Communications Kit and Air-Source / Water-Source Unit
No communication signal for more than five (5) consecutive
minutes from AHU Communications Kit to the Air-Source /
Water-Source Unit.
CH06 Pipe Out Thermistor Error
Pipe out thermistor has disconnected from AHU, or has short
circuited.
Table 14: Error Code Table.
Error Codes
• The error code function indicates when an operation failure occurs in the system, and provides self-diagnosis about the type of error.
• The error code is displayed on the wired remote controller and the control board LED on the air-source / water-source unit.
• If two or more two errors occur simultaneously, the smallest of the error code numbers is displayed first.
• When the problem causing the error code to appear is fixed, then the error code will immediately stop displaying on the LED.
TROUBLESHOOTING