5. Trouble Shooting
6.19 Check code Trouble shooting CH32, CH33
32
33
D-pipe (Inverter)
temp. high
(105˚C )
D-pipe (Constant)
temp. high
(105˚C )
Discharge sensor
(Inverter) temp. high
Discharge sensor
(Cons.) temp. high
Check the discharge pipe sensor for INV.
Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Refer to sensor resistance table.
Check the discharge pipe sensor for Cons.
Check the install condition for over load.
Check the leakage of refrigerant.
Check the SVC V/V open.
Refer to sensor resistance table.
Display
code
Title Cause of error Check point & Normal condition
Is the resistance of the
sensor is 200k
at 25˚C?
Plug the sensor
on Indoor unit PCB
Estimate the Voltage
of each sensor.
Repair or Change the PCB.
Check Over load condition
- Refrigerant leakage
- Condenser is blocked
- Outdoor fan is locked
Unplug the sensor
on Outdoor unit PCB
Check the
Connector connection
Estimate the resistance
of each sensor.
Is it normal ?
Yes
Yes
No
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
Yes
Yes
Yes
No
Change the sensor
Is the voltage of the
sensor is
4.5Vdc at 25˚C
No
Change the sensor
No
Correct connection
Check Flow Chart