5. Trouble Shooting
6.12 Check code Trouble shooting CH22
Check Over load condition
- Overcharging of
refrigerant
- Pipe Length
- Condenser is blocked
- Outdoor fan is locked
Is it normal ?
(1 Ph : 230V ±10%
3 Ph : 400V ±10% )
Change Main PCB
Check the wire
connection.(U,V,W)
Is it normal ?
Check the resistance of
comp. (No difference at
each terminal)
Is it normal ?
Yes
Yes
No
Correct
connection
Yes
No
Needs electric work
Check DC link
capacitor Is it normal?
(Refer to belows)
Yes
No
No
Change DC link
capacitor
Or Main PCB
Remove obstruction
Change outdoor fan
or motor
Change refrigerant
No
Change
Compressor
Check the electricity
leakageof the compressor.
(Refer to comp check table)
Check the input power
(Outdoor, Indoor unit)
Is it normal ?
Yes
No
Change
Compressor
Check Flow Chart
Dc link voltage table
Type Non operating Operating
1 Phase AUUW126C PSC DC300V ± 10% DC280V ± 10%
AUUW186C PSC DC300V ± 10% DC280V ± 10%
AUUW246D PFC DC300V ± 10% DC380V ± 10%
AUUW306D PFC DC300V ± 10% DC380V ± 10%
AUUW366D PFC DC300V ± 10% DC380V ± 10%
AUUW426D PFC DC300V ± 10% DC380V ± 10%
AUUW486D PFC DC300V ± 10% DC380V ± 10%
AUUW606D PFC DC300V ± 10% DC380V ± 10%
3 Phase AUUW368D PSC DC540V ± 10% DC500V ± 10%
AUUW428D PFC DC540V ± 10% DC680V ± 10%
AUUW488D PFC DC540V ± 10% DC680V ± 10%
AUUW608D PFC DC540V ± 10% DC680V ± 10%
Model
DC Link Voltage
22
Max. C/T
Over current
Malfunction of compressor
Blocking of pipe
Low voltage input
Refrigerant, pipe length, blocked,
Display
code
Title Cause of error Check point & Normal condition