5. Trouble Shooting
6.14 Check code Trouble shooting CH24
Is the wire connection
normal ?
Is the SVC Valve
opened ?
Check the leakage of
refrigerant.
Check Pressure of
suction pipe
Check Pressure of
discharge pipe
Is the soldering
state of connector is
normal?
Yes
Yes
No
Correct connection
No
Re-soldering component
Yes
No
Open SVC Valve
Is it normal ?
Change main PCB
Yes
No
Re-vaccuming system
& Re-charging
Check Flow Chart
CN_PRESS
Switch Low pressure switch High pressure switch
Spec 0.03 Mpa 4.3 Mpa
Model AUUW126C AUUW246D
AUUW186C AUUW306D
AUUW366D
AUUW426D
AUUW486D
AUUW606D
AUUW368D
AUUW428D
AUUW488D
AUUW608D
Pressure switch table
24
Press S/W Open
Low / High press
S/W open.
Check the connection of CN_PRESS
Check the SVC V/V open.
Check the leakage of refrigerant.
Display
code
Title Cause of error Check point & Normal condition