Code Item Detail Remark
05 Function Setting temperature selection
Description Selection for setting temperature as air temperature or
leaving water temperature.
Value #1 Note 01:Air temperature
02:Leaving water temperature
Air temperature as setting temperature is ONLY available
when remote air sensor.
Connection is enabled and Function code 03 is set as 02.
Default 2
Range 01 ~ 02
Value #2 Note -
Default -
Range -
06 Function Auto dry contact
Description
Setting dry contact auto start option.
If thermostat is used, value should be changed from "2" to "1".
Value #1 Note 01: Auto start off
02: Auto start on
Default 2
Range 01 ~ 02
Value #2 Note -
Default -
Range -
07 Function Address setting
Description Assigning address when central controller is installed
If thermostat is used, value should be changed from "2" to "1".
Value #1 Note -
Default 00
Range 00 ~ FF
Value #2 Note -
Default -
Range -