Code Item Detail Remark
2B Function Sanitary water heating timers
Description
Value #1 Note
Default
Range 5 ~ 95 min (step: 5 min)
Value #2 Note
Default
30 min
Range 0 ~ 600 min (step: 30 min)
180 min
Determine following time duration : operation time of sanitary tank
heating, stop time of sanitary tank heating, and delay time of
sanitary tank heater operating.
This time duration defines how long time sanitary tank heating can
be stopped. It is also regarded as time gap between sanitary tank
heating cycle.
Value #3 Note
Default
Range 20 ~ 95 min (step: 5 min)
20 min
This time duration defines how long time sanitary tank heater
will not be turned on in sanitary water heating operation.
This time duration defines how long time sanitary tank heating can
be continued.
2E
2F
Function Changing thermal on / off room air temp
Description Select Thermal on / off Temperature gap.
Value #1 Note
0
1
2
3
-0.5 °C
4 °C
2 °C
-1 °C
1.5 °C
6 °C
4 °C
1 °C
Thermal on Thermal off
Default
0
Range
0 ~ 3
Function Changing thermal on / off leaving water Ten
Description Select Thermal on / off Temperature gap.
Value #1 Note
0
1
2
3
-2 °C
-6 °C
-2 °C
-1 °C
2 °C
4 °C
4 °C
1 °C
Thermal on Thermal off
Default
0
Range
0 ~ 3