Installation
11
2.0 INSTALLATION
2.1 Unpacking and Inspection
Unpack the UPS and conduct the following checks:
Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and
your local dealer or your Emerson representative immediately.
Check the accessories included in packaging list. If there is any discrepancy, contact your local
dealer or your Emerson representative immediately.
2.2 What’s Included
With GXT3 UPS
Compact Disk with:
Liebert MultiLink
®
Configuration Program
User Manual
Terminal Block Communication terminals
USB Cable: one, 6-1/2 ft. (2m) long
Mounting hardware, including screws and handles
Plastic tower stand sets: 2 (four pieces)
Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
2.3 Preparation for Installation
2.3.1 Installation Environment
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned Off.
The installation environment should meet the specifications listed in 9.0 - Specifications).
Place it in an area of unrestricted airflow around the unit, away from water, flammable liquids,
gases, corrosives, and conductive contaminants. Avoid direct sunlight.
Installation Clearances
Maintain at least 4 inches (100mm) clearance in the front and rear of the Liebert GXT3. Do not
obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces
ventilation and heat dissipation, shortening the service life of the Liebert GXT3.
NOTE
The GXT3 External Battery Cabinet shipping package includes one battery cabinet, two
spacers for tower configuration and one DC power cable.
NOTE
Operating the Liebert GXT3
in temperatures above 77°F (25°C) reduces battery life.

Table of Contents

Other manuals for Liebert GXT3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert GXT3 and is the answer not in the manual?

Liebert GXT3 Specifications

General IconGeneral
ModelLiebert GXT3
TypeOnline Double Conversion
Frequency50/60 Hz
Power Factor0.9
Battery TypeSealed Lead-Acid (SLA)
Form FactorTower
Communication InterfaceUSB, RS-232
Input Voltage120V
Output Voltage120V