Operation with Advanced Microprocessor with Graphics Control 19
3.4.4 Setup Custom Alarms
Selecting SETUP CUSTOM ALARMS will step to the following menu:
SETUP CUSTOM ALARM TEXT
CHANGE CUSTOM TEXT 1
CHANGE CUSTOM TEXT 2
CHANGE CUSTOM TEXT 3
CHANGE CUSTOM TEXT 4
The custom alarm messages can be selected from a list of standard messages or you can write your
own messages. The message selected for any custom alarm can be changed at any time by selecting
SETUP CUSTOM ALARM TEXT. A list of 5 standard messages (see list below) and 4 custom mes-
sages are available to choose from. To modify the custom messages press CHANGE CUSTOM TEXT 1
(2, 3 or 4). Each message can be up to 20 characters in length and can be any of the following charac-
ters (or a blank space): ABCDEFGHIJKLMNOPQRSTUVWXYZ#%*-0123456789.
Standard custom alarm messages:
WATER UNDER FLOOR
SMOKE DETECTED
STANDBY GC PUMP ON
LOSS OF WATER FLOW
STANDBY UNIT ON
For more information concerning alarms, see 5.0 - Alarm Descriptions.
3.4.5 View Water Detect Floor Plan (for Optional LTM1000/LT750)
When water is detected the alarm will sound and the WATER UNDER FLOOR alarm message will be
displayed. To see where the water is in the room, select VIEW/SET ALARMS from the main menu,
then VIEW WATER DETECT FLOOR PLAN. A tile will be highlighted and blinking to indicate the
position of the detected water.
3.4.6 Setup Water Detect Floor Plan
The selected (i.e. cursor) floor tile will be highlighted and blinking. The UP and DOWN arrow keys
are used to position the cursor tile. The UP key will move the cursor tile up and then it wraps around
to the bottom of the next column to the right. The DOWN arrow key moves the cursor down, then to
the top of the next column to the left. The cursor will also wrap around from the right top tile to the
left bottom tile and back.
There are three different types of tiles to be defined: the environmental unit, the LT750 and sensor
cable tiles. To setup the cable layout, first move the cursor to the location of the environmental unit
and press the ENTER key. A rectangular box will be drawn at that location. Then move the cursor to
the location of the LT750 and press the ENTER key. A solid circle will be drawn on the display. No
tile can have two definitions, so if the LT750 is physically directly under the unit it has to be defined
at least one tile away.
The sensor cable should not be defined one tile at a time. The only sensor cable tiles that need to be
defined are the tiles where the cable is going to change direction, and the last tile. The display will
automatically define any tiles between two consecutively defined sensor tiles to be sensor tiles.
The ENTER key is also used to undo tile definitions. If a tile is defined in the wrong place, position
the cursor on that tile and press the ENTER key. It will undefine the tile under the cursor and move
the cursor back to the last defined tile. The entire layout can be erased by successively pressing the
ENTER key. When the last tile is defined, press the ESCape key to leave the setup screen.
For more information and detailed installation instructions, see 4.5.2 - Water Detection Display.