EasyManua.ls Logo

Liebert himod - Suction Pressure; Discharge Pressure; Superheat; Thermostatic Expansion Valve

Liebert himod
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Component Operation and Maintenance 41
6.4.1 Suction Pressure
Suction pressure will vary with load conditions. The low pressure switch will shut the compressor
down if suction pressure falls below the cut-out setting. High suction pressure reduces the ability of
the refrigerant to cool compressor components and can result in compressor damage. Minimum (pres-
sure switch cut-out setting) and maximum (design operating) suction pressures are in Table 16.
6.4.2 Discharge Pressure
Discharge Pressure can be increased or decreased by load conditions or condenser efficiency. The high
pressure switch will shut the compressor down at its cut-out setting. Refer to Table 17.
6.4.3 Superheat
Himod units are designed for high sensible heat ratios. At design conditions, suction superheat values
in the range of 20-35°F (11-19°C) can be expected.
Superheat can be adjusted by the Thermostatic Expansion Value (TEV).
To determine superheat:
1. Measure the temperature of the suction line at the point the TEV bulb is clamped.
2. Obtain the gauge pressure at the compressor suction valve.
3. Add the estimated pressure drop between bulb location and suction valve.
4. Convert the sum of the two pressures to the equivalent temperature.
5. Subtract this temperature from the actual suction line temperature. The difference is superheat.
6.4.4 Thermostatic Expansion Valve
Operation
The thermostatic expansion valve performs one function. It keeps the evaporator supplied with
enough refrigerant to satisfy load conditions. It does not effect compressor operation.
Proper valve operation can be determined by measuring superheat. If too little refrigerant is being fed
to the evaporator, the superheat will be high; if too much refrigerant is being supplied, the superheat
will be low. The correct superheat setting is in the range of 20-35°F (11-19°C).
Adjustment
To adjust the superheat setting, proceed as follows:
1. Remove the valve cap at the bottom of the valve.
2. Turn the adjusting stem counterclockwise to lower the superheat.
3. Turn the adjusting stem clockwise to increase the superheat.
Table 16 Suction pressures
System
Minimum
PSIG (kPa)
Maximum
PSIG (kPa)
Air Cooled 20 (138) 90 (620)
Water Cooled 20 (138) 90 (620)
Glycol Cooled 20 (138) 90 (620)
Table 17 Discharge pressures
System Design
Discharge Pressure
PSIG (kPa)
Air Cooled 260 (1795)
Glycol Cooled
65-75
°F (18-24°C) fluid 210 (1450)
85
°F (29°C) fluid 225 (1550)
115
°F (46°C) fluid 295 (2035)
Maximum 330 (2275)
High Pressure Cut-Out 360 (2482)
NOTE
Make no more than one turn of the stem at a time. As long as 30 minutes may be required for
the new balance to take place.

Table of Contents

Other manuals for Liebert himod

Related product manuals