lifebreath.com 21
18 TIMERS
20/40/60 Minute Timer (99-DET01)
Connect the wires from the Y, R, and G terminals on the timer to the 4 (YEL), 3 (RED), and 5 (GRN)
terminals on the HRV terminal block as shown. A jumper between Red and On is required when not
using a de-humidistat.
Mechanical Timers Installation (99-101)
The Mechanical Timer is a 2 wire “dry contact” timer. Connect a jumper wire between the 2 (ON) and
3 (RED) terminals on the HRV terminal block and connect the two timer wires to the 2 (ON) and 6
(HI) terminals on the HRV terminal block as shown.
Attention
Timers mount in standard electrical boxes.
Use 3 wire 20 gauge (min.) 100 ft length (max.) low voltage wire and multiple timers individually wired
back to the unit.