continues when the output current drops
15% below the value set in P3-01.
Stall Prevention
Level during
Acceleration
Sets the output current level to activate the
Stall Prevention function during acceleration.
Default: Determined
by A1-06
Min.: 0%
Max.: 180%
Stall Prevention
Limit during
Acceleration
Sets the lower limit of Stall Prevention in the
constant power range as a percentage of the
drive rated output current.
Default: 50%
Min.: 0 %
Max.: 100 %
Stall Prevention
during
Deceleration
0 : Disabled
The drive decelerates according to the set
deceleration time
1 : Enabled (Without Braking Resistor)
2: Overexcitation deceleration but no stall
prevention
3: Overexcitation deceleration includes stall
prevention
Stall Prevention
Level during
Deceleration
Sets the voltage level to activate the Stall
Prevention function during deceleration.
Default: 200V Series:
395 V
400V Series:
10HP or less 790V
15HP or more 750V
Min.: 330V
Max.: 410V <3>
Stall Prevention
during Run
0 : Disabled
1 : Enabled (Deceleration Time 1)
2 : Enabled (Deceleration Time 2)
Default: 1
Range: 0, 1, 2
Stall Prevention
Level during Run
Sets the current level to activate the Stall
Prevention function during run.
Default: Determined
by A1-06
Min.: 0%
Max.: 180%
Accelerated stall
prevention
current
detection
interval
Acceleration stall prevention function, the
corresponding current detection range, if the
current is less than P3-01-P3-11, it will
accelerate according to the normal
acceleration time
Default: 15%
Range: 0% to 180%
Stall prevention
current
detection
interval during
operation
Prevent function during operation,
corresponding current detection range. If the
current is less than P3-06-P3-12, stall
prevention function during operation will be
ended and normal operation
Default: 10%
Range: 0% to 180%