Time 3
(Acceleration
Time 1 for Motor
2)
0Hz to the maximum output.
Deceleration
Time 3
(Deceleration
Time 1 for Motor
2)
Sets the time that the drive decelerates from
the maximum output to 0Hz.
Acceleration
Time 4
(Acceleration
Time 2 for Motor
2)
Sets the time that the drive accelerates from
0Hz to the maximum output.
Deceleration
Time 4
(Deceleration
Time 2 for Motor
2)
Sets the time that the drive decelerates from
the maximum output to 0Hz.
Sets the time to stop the drive faster.
Acc./Dec. Time
Unit Selection
Set the units of time for C1-00 to C1-08.
0 ∶ 0.01 s (0.00 to 600.00 s)
1 ∶ 0.1 s (0.00 to 6000.0 s)
Default∶ 1
Min.: 0
Max.: 1
Acc./Dec. Time
Switch
Frequency
Sets the frequency level. The drive will switch
the acceleration and deceleration time at this
level.
Default: 0.0 Hz
Min.: 0.0 Hz
Max.: <5>
Sets the time to accelerate from 0 Hz to Jog
Frequency Command (L1-16).
Default: depends on
the HP
10HP and below: 10s
15HP and 20HP: 15s
25HP and above: 20s
Min.: 0.0 s
Max.: 6000.0 s
Sets the time to decelerate from Jog
Frequency Command (L1-16) to 0 Hz.
Default: depends on
the HP
10HP and below: 10s
15HP and 20HP: 15s
25HP and above: 20s
Min.: 0.0 s
Max.: 6000.0 s