97
Sets the time to decelerate during KEB function.
Default: 0.0 s
Min.: 0.0 s
Max.: 6000.0 s
Acceleration Time
after KEB
Sets the time to reaccelerate from the speed
when KEB function was deactivated to the set
frequency command (operation frequency before
power loss).
When set to 0.0 s, the drive will accelerate to the
previously active frequency according to the
active acceleration time set by any of C1-00,
C1-02, C1-04 or C1-06.
Default: 0.3 s
Min.: 0.0 s
Max.: 6000.0s
Emergency stop
setting level before
power failure
By setting the P2-06 level, when the voltage level
is detected to be lower than P2-06, the inverter
will decelerate according to the C1-08 emergency
stop time until it is lower than the P2-03 UV
detection value.
According to the
model, the 200V model
is 150~280, and the
400V model is
300~560.
Sets the minimum duration of KEB operation after
activation.
KEB function will operate according to this
detection time even if power recovers within this
duration.
Default: 50 ms
Min.: 0 ms
Max.: 2000 ms
Voltage Target
During KEB
Sets the target value for the main circuit DC
voltage or to deactivate KEB.
Default: Depending on
d1-00
D1-00 is greater than
400V for 500V, less
than 400V for 460V
0 : KEB Operation Method 1
1 : KEB Operation Method 2
2 : KEB Operation Method 3
Default: 0
Range: 0, 1, 2
Emergency stop
action selection
before power
failure
Stall Prevention
during Acceleration
0 ∶ Disabled
1 ∶ Enabled the value set in P3-01.
Acceleration stops when the output current
exceeds the value set in P3-01. Acceleration