137
Keypad
Display
Error Name
Cause
Possible Solution
2
4. L2-01 ≠ 0 when b5-00 = 3
or 4
oPE10
V/F Data Setting
Error
d1-02, d1-04, d1-06,
d1-08, d1-10 (or
d1-13, d1-15, d1-17,
d1-19, d1-21)
incorrect settings
V/F parameters setting
incorrect
Correct the setting in d1-02, d1-04,
d1-06, d1-08 and d1-10 (or d1-13,
d1-15, d1-17, d1-19 and d1-21).
oPE11
Carrier Frequency
Setting Error
1. Contradictory settings
· C6-03 (Carrier Frequency
Proportional Gain)6
· C6-02 (Minimum Carrier
Frequency) C6-01
(Maximum Carrier Frequency)
Note: If C6-03 ≤ 6 , the drive
operates at C6-01
2. The limit set in C6-00 to
C6-03 are contradictory
Correct the parameter setting.
oPE12
Reference Sample &
Hold frequency
command error
When the DI command is set
to 61, other groups of DIs are
set to 10~13, 18 or 53~55.
Sets the parameters correctly.
oPE13
Frequency stack
setting error
When b1-09 is reserved for
the frequency superposition
function, its b1-00 and b1-07
are set to the same source.
Sets the parameters correctly.
oPE14
Incorrect Jump
Frequency Setting
The setting does not
followL3-00<=L3-01<=L3-02
Correct the setting.
oPE15
Torque Control
Setting Error
The following are set when
A1-02 = 3 or 5 (Closed-Loop
Vector Control)
· L5-00 = 1 and E1-□□ = 70
· L5-00 = 1 or E1-□□ = 70, and
E1-□□= 58 or 59
· L5-00 = 1 or E1-□□ = 70
Correct the parameter setting.
oPE16
Retain
oPE17
Rated speed of
motor incorrect
1. The rated motor speed is
set to exceed the
synchronous speed of the
motor.
1. Correctly set the motor base
frequency and motor pole count
2. Correctly set the rated motor speed