103
will be shut off the motor will coast resulting uncontrolled motor state. To avoid this, set an appropriate
deceleration time to C1-08.
23 to 38 : External Fault
Stops the drive when problems occur with external devices.
To use the external fault function, set E1-00 to E1-05=23 to 38. While an external fault is
triggered, EF□ will be displayed on the keypad where □ is the number of the terminal assigned
to the external fault signal. For example, if an external fault signal is input to terminal S3, then
EF3 will be displayed.
Selects the value to set to E1-□□ from a combination of the following three conditions:
· Input signal from peripheral devices
· Detection method of external fault
· Stopping method (for external fault detection)
The following table shows the combination of the conditions.
Alarm Only
(continue
operation)
<1> Determine the terminal status to detect the fault. (Normal Open: detection when terminal closed, normal
closed: detection when terminal open)
<2> Determine the detection should be enabled only during run or always detected.