145 
 
1 ∶ Time of Run   
Keeps track of time when the output voltage is active.   
  o4-06  U2 Reset Setting 
Resets the data for U2-□□ (Fault Information) as this data will not be reset by A1-03 (Reset). 
0 : No Action   
The data for the U2-□□ (Fault Information) monitor will not be reset.   
1 : Enabled 
Resets the data for the U2-□□ (Fault Information) monitor. Set this value to 1 and press ENTER 
will clear all the fault information to 0.   
  o4- 07 to o4-08  Retain   
6.9 Group t, Auto-Tuning 
t1 IM Motor Auto-Tuning 
t1 parameters set the data for IM motor Auto-Tuning   
Note:    When running variable speed motors or vector motors, the voltage or frequency may 
be lower than general-purpose motors. Therefore set the motor data according to the motor 
nameplate and perform Auto-Tuning. After that, change the maximum output frequency in 
d1-02.   
  t1-01  Auto-Tuning Method Selection 
Selects the method of Auto-Tuning..   
Auto-Tuning Method Selection 
0 : Rotational Auto-Tuning 
1 : Stationary Auto-Tuning 1 
  t1-02  Motor Output Power