9.2.8 Main Circuit- Resistors
Inspection Points
Corrective Action
Inspection Cycle
Daily
6
months
12
months
Any odor or crack because of heat?
It is normal if the color changes
slightly.
Check the connection if the color
changes.
Any disconnection?
Any damage at the connection?
9.2.9 Main Circuit- Magnetic Contactors & Relays
Inspection Points
Corrective Action
Inspection Cycle
Daily
6
months
12
months
Any noise during operation?
Check the circuit voltage respectively
when the voltage exceeds or is within
the tolerance.
Replace the damaged MC, relay or
board.
Any damage at the connection?
9.2.10 Control Circuit- Control Boards & Connectors
Inspection Points
Corrective Action
Inspection Cycle
Daily
6
months
12
months
Are the screws and connectors all
tightened
Fix the loose connections.
Replace the board if an antistatic cloth
or vacuum plunger cannot be used.
Do not use any solvents to clean the
board.
Remove the dust with a vacuum
cleaner.
Replace the entire drive if the
component is impossible to be
clearned or replaced.
Any odor or color change because of
heat?
Any crack, damage, shape change or
rust?
Any liquid leakage or swell at the
capacitor?

Table of Contents

Other manuals for LiteOn EVO600043S1D5E20F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LiteOn EVO600043S1D5E20F and is the answer not in the manual?

LiteOn EVO600043S1D5E20F Specifications

General IconGeneral
BrandLiteOn
ModelEVO600043S1D5E20F
CategoryController
LanguageEnglish

Related product manuals