106 
 
65 : DC Braking   
Stops the motor during deceleration. When a Run command or Jog command is entered, the 
DC braking will be removed as illustrated in the following figure. Refer to b2 (DC Braking) for 
details.   
Output 
frequency
Run 
command
DC braking 
command
ON
ONOFF
OFF
OFF
OFF
DC braking
DC Braking 
Start Level
( b2-00 )
DC braking
 
Figure 6.52 DC Braking Operation 
66 to 68:    Retain   
69 : Drive Enabled 
The drive does not accept any Run command until the input terminal closes. When the input 
terminal is open, the keypad will display  “DNE”. 
If a Run command is entered before the assigned terminal closes, then drive will not run until 
the Run command is cycled. If the terminal is open during run, the drive will stop according to 
b1-02 (Stopping Method Selection). Refer to b1-02 for details.   
70 to 73: Retain   
E2  Multi-Function Digital Output 
  E2- 00  Relay 1   
The  drive  has  four  multi-function  output  terminals.  Assign  the  functions  to  E2-00  to  E2-03 
according to Table 6.20.   
Relay 1 Function Selection