24 
 
and W respectively. Ensure the motor and drive terminals are in same phase sequence or 
the motor will rotate reversely.   
  Do not connect power cable to output terminals of the drive. Failure to comply could 
cause drive damage and a fire.   
 
4.2.2.3 Braking Unit Terminal: 
 
  If the drive is used in a high-frequency or heavy duty application which requires frequent 
braking or shorter deceleration time, install an optional braking unit to increase the 
braking torque. 
 
  Please refer to the wiring diagram when installing braking unit.   
4.2.2.4 Ground Terminal 
  Use grounding cables of dimensions regulated by electrical equipment standard. Shrink 
wiring distance to prevent leakage current resulting unstable electrical potential at the 
terminal distant from grounding terminal.   
  Do not use share the same grounding cable with welding machines or any device 
requiring large current. Failure to comply could cause drive or equipment malfunction. 
  Do not wind the grounding cable when multiple drives are installed. Failure to comply 
could cause drive or equipment malfunction. 
  Ensure the neutral of the input side and drive terminal "    “ are grounded 
according to the local electrician regulations. 3WYE (e.g. TN and TT) system are 
suggested for the drive primary side. 
4.2.2.5 Jumper   
  EVO6000 complies with the European LVD standard EN 61800-5-1 (2007) reducing the 
current leakage to below 10mA DC under testing condition regulated by IEC 60990 
(1999).