temperature is too
high downtime
When this signal is effective and normal operation, If
the temperature is too high, controller high-speed
cooling delay until after the downtime; When this signal
is invalid, If there is high temperature, the controller
directly to the high-speed stop.
Sensor selection (table 4)
7.4. SENSOR SELECT (TABLE 4)
0 Not used
1 Digital input low effective
2 Digital input high effective
3 VDO 120℃
4 CURTIS
5 VOLVO-EC
6 DATCON
7 SGX
8 SGD
9 SGH
10 PT100
Digital input is the switch signal, can
choose low level or high level, grounding is
low level, suspend in midair is the high
level, not plugged into a power supply for
the Cathode. Defined resistive range is
0-999.9 Ω, the factory default is SGD
sensor.
0 Not used
1 Digital input low effective
2 Digital input high effective
3 VDO0-10BAR
4 CURTIS
5 VOLVO-EC
6 DATCON?10BAR
7 SGX
8 SGD
9 SGH
Digital input is the switch signal, can
choose low level or high level, grounding is
low level, suspend in midair is the high
level, not plugged into a power supply for
the Cathode. Defined resistive range is
0-999.9 Ω, the factory default is SGD
sensor.
0 Not used
1 Digital input low effective
2 Digital input high effective
3 VDO0-180ohm
4 SGD
5 SGH
Digital input is the switch signal, can
choose low level or high level, grounding is
low level, suspend in midair is the high
level, not plugged into a power supply for
the Cathode. Defined resistive range is
0-999.9 Ω,the factory default is no sensor.
In setting fuel level sensor type when,
Should put the programmable input port
type is set to 0, then set the fuel level
sensor type.