LXC706 Series Genset Controller
Dongguan Tuancheng Automation Equipment Co.,Ltd.
LXC706 Product User Manual Dongguan Tuancheng Automation Equipment Co.,Ltd.
: +86-769-23836636 : F:+86-769-23166296 : www.lixise.com
Page
12
of
17
P33
Disconnect
Engine Speed
(0-3000)RPM
360RPM
When engine speed higher than the set value, starter
will be disconnected.
P34
Disconnect Oil
Pressure
(0-400)kPa
200kPa
When generator oil pressure higher than the set value,
starter will be disconnected.
P35
D+
Disconnect
(3.0-32.0)V
8.0V
When generator D+ higher than the set value, starter
will be disconnected.
P36
Temp. Sensor
Curve
(0-10)
3
VDO120 ºC
P37
Oil Pressure
Sensor Curve
(0-9)
3
VDO0-10BAR
P38
Fuel sensor
(0-5)
0
not used. (Using the fuel level sensor will switch input
port is set to unused)
P39
Temperature
Sensor Open
(0-2)
0
0: Never (temperature sensor will show “+++”);
1:Warn; 2:Shutdown
P40
Oil Pressure
Sensor Open
(0-2)
0
0: Never (temperature sensor will show “+++”);
1:Warn; 2:Shutdown
P41
Fuel sensor open
(0-1)
0
0: Never (temperature sensor will show “+++”);
1:Warn;
P42
Device ID
1-247
1
P43
Power On Mode
0-2
0
0
Stop Mode 1
Auto mode 2
Manual Mode
P44
technician
password
0-9999
0000
P45
operator
password
0-9999
1111
7.2. PROGRAMMABLE OUTPUT (TABLE 2)
No.
ITEM
Description
0
Not Used
When selected, the output port is not output.
1
Common Alarm
Includes all stop alarm and warning alarm, when only warning alarm
input, this alarm is not self-locking, when outage alarm occurs, the
alarm self-locking, until the alarm is reset.
2
ETS Control
Used for engines with ETS electromagnet. Pull in when stop idle is
over and pull out when set“ETS delay”is over.
3
Idle Control
Used for engine which has idles.Pull in before starting and pull out
after into hi-speed warming; Pull in during stopping idle mode and pull
out after shutdown completed.
4
Preheat Control
Before the boot is closed, power is disconnected before starter.
5
Close Generator
Generator load conditions are ripe for action.
6
Reserved
7.3. PROGRAMMABLE INPUT (ACTIVE WHEN CONNECT GND (B-) (TABLE 3)
No.
ITEM
Description
0
Switch
input
Not Used
1
Aux High Temp
In after the success of the generator starting, if the
signal is effective, generator alarm and shutdown
immediately
2
Aux Low OP
3
Low fuel
If the signal is effective, warn only, not shutdown
4
External stop
generators
If the signal is effective, warn only, not shutdown