25
3.9 Advanced Setup
The “ADVANCED SETUP” screens allow for the special conguring
of the controller for advanced options. These options include:
FLOW ALARM (energizing the alarm output relay on loss of ow);
FLOW SENSE (under FLOW ALARM) the response of the ow switch
may be changed from either normally open or normally closed logic;
TRIP (bleed based on either rising or falling conductivity trip point);
4 - 20 mA recorder output programming;
Conductivity units DISPLAY may be either µSiemens or PPM/TDS;
BLEED control (Boiler or Cooling Tower); and
LOAD DEFAULTS.
ADVANCED SETUP
FLOW ALARM (ON)
TRIP ( )
4-20 MA
DISP UNITS (ΜS)
CONTROL (CLGTWR)
LOAD DEFAULTS
EXIT
ADVANCED SETUP
<
ENTER
CONDUCTIVITY
SET POINT
LOW ALARM
HIGH ALARM
FEED
MANUAL OUTPUT
ADVANCED SETUP
TEMPERATURE
H
2
O METER
DIFFERENTIAL
BOILER