3.12 Boiler
The DC4000 Controller is shipped from the factory set in the “COOL-
ING TOWERmode. Select BOILERmode in ADVANCED” menu
to change this.
CONDUCTIVITY
SET POINT
LOW ALARM
HIGH ALARM
FEED
MANUAL OUTPUT
ADVANCED SETUP
TEMPERATURE
H
2
O METER
DIFFERENTIAL
BOILER
FLOW ALARM (ON)
TRIP ( )
4-20 MA
DISP UNITS (ΜS)
CONTROL (CLGTWR)
LOAD DEFAULTS
<
COOLING TOWER / BOILER
Now the “BOILER” screen will appear in the “MAIN” menu.
Navigate to this screen.
BOILER
Use or to toggle from CONTINUOUSor TIMED
conductivity sampling. Press to select that mode.
• If “CONTINUOUS” sampling is selected, proceed to
Section 4 “Continuous Sampling Start-Up”.
• If “TIMED” sampling is selected, the operator will then
have the following options:
CONDUCTIVITY
SET POINT
LOW ALARM
HIGH ALARM
FEED
MANUAL OUTPUT
ADVANCED SETUP
TEMPERATURE
H
2
O METER
DIFFERENTIAL
BOILER
ENTER
ENTER
ENTER
ENTER
CONTINUOUS / TIMED
(866) 433-6682 • (281) 359-8538 • sales@novatech-usa.com • www.novatech-usa.com

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LMI Technologies Liquitron DC4000 Series and is the answer not in the manual?

LMI Technologies Liquitron DC4000 Series Specifications

General IconGeneral
BrandLMI Technologies
ModelLiquitron DC4000 Series
CategoryController
LanguageEnglish

Related product manuals