Guide for troubleshooting for PS2 pump controller
Surge Protector version 1
• Check the resistance between the
NO/NC and the opposite wire and the
COM and the opposite wire
• Both resistance values should be approx.
100Ω
• Connect the positive measuring grabber
clip to NO/NC and COM
• Depending on the multimeter it should
show several kΩ or several 10kΩ
• Switch the multimeter to diode mode
and keep the connection like the test
before
• The value should show infinite or open
loop