Guide for troubleshooting for PS2 pump controller
Surge Protector Version 2
If any of these test shows a different value, the Surge Protector2 needs to be replaced.
• Similar to the previous version check the
resistance between the negative - wire
(black) and the opposite terminal then
positive + wire (red) and its opposite
terminal.
• Both resistance values should be approx.
100Ω
• Connect the positive measuring grabber
clip to positive + wire and COM to
negative - wire.
• Depending on the multimeter it should
show several MΩ or open loop