Guide for troubleshooting for PS2 pump controller
If a proper voltage is present, the validity of the sensor needs to be confirmed. The analog input
of the controller uses 4-20 mA signals. Therefore, the current needs to be checked. The current
is measured in series as shown in the following connection overview:
• Configure your multimeter
o Choose current mA-
measurement
o Connect the measuring clips as
shown above