Chapter 2 Specifications
2-1
Chapter 2 Specifications
2.1 General Specifications
General specifications of XGT series
No. Item Specification Related specifications
1
Operating
temperature
0+55℃∼ ℃ -
2
Storage
temperature
-25 +70℃∼ ℃ -
3
Operating
humidity
595%RH, ∼ Non-condensing -
4 Storage humidity 5 95%RH, ∼ Non-condensing -
For discontinuous vibration -
Frequency Acceleration Amplitude Number
10≤f< 57㎐ - 0.075mm
57≤f≤150㎐ 9.8m/s2 (1G) -
For continuous vibration
Frequency Acceleration Amplitude
10≤f< 57㎐ - 0.035mm
5 Vibration
57≤f≤150㎐ 4.9m/s2 (0.5G) -
Each 10 times in X,Y,Z
directions
IEC61131-2
6 Shocks
* Maximum impact acceleration:147㎨(15G)
* Authorized time :11㎳
* Pulse wave : Signal half-wave pulse (Each 3 times in X,Y,Z
directions)
IEC61131-2
Square wave impulse noise ±1,500V
Test specifications of LS
Industrial Systems
Electrostatic discharging Voltage : 4kV (contact discharging) IEC 61131-2, IEC 61000-4-2
Radiated electromagnetic field noise 27 ~ 500MHz, 10 V/m IEC 61131-2, IEC 61000-4-3
Class Power module
Digital/
Analog I/O
communication interface
7 Impulse Noise
Fast
Transient
/ burst
noise
Voltage 2kV 1kV
IEC 61131-2,
IEC 61000-4-4
8
Ambient
conditions
No corrosive gas or dust -
9 Operating height 2,000m or less -
10
Pollution
degree
2 or less -
11 Cooling type Natural air cooling -
Notes
1) IEC(International Electrotechnical Commission):
An international nongovernmental organization which promotes internationally cooperated standardization in electric/electronic
fields, publishes international standards and manages applicable estimation system related with.
2) Pollution degree:
An index indicating pollution level of the operating environment which decides insulation performance of the devices. For
instance, Pollution level 2 indicates the state generally that only non-conductive pollution occurs. However, this state contains
temporary conduction due to dew produced.