Chapter 8 Troubleshooting
8-1
Chapter 8 Troubleshooting
How to shoot the troubles on the high speed counter module will be described.
8.1 Error code
Errors of the high speed counter module are as described below.
Error code
(Dec)
CH0 CH1
Description
RDY LED
status
10 Module error (ASIC Reset error)
11 Module error (ASIC Memory error)
12 Module error (ASIC Register error)
Blinks every
0.2 sec.
20 120 Counter type range exceeded
21 121 Pulse input type range exceeded
22 122 Auxiliary Mode type range exceeded
23 123 Sampling Count value range exceeded
24 124 Compared output0 type range exceeded
25 125 Compared output1 type range exceeded
26 126 Preset value exceeded counter range
27 127 Ring counter minimum. value Ring counter maximum value input
28 128 Compared output 0 minimum value exceeded maximum input range
29 129 Compared output 0 maximum value exceeded maximum input range
30 130 Compared output 0 minimum value > compared output 0 maximum value set
31 131 Compared output 1 minimum value exceeded maximum input range
32 132 Compared output 1 maximum value exceeded maximum input range
33 133 Compared output 1 minimum value > compared output1 maximum value set
34 134 Pulses per revolution range exceeded
35 135 Frequency input mode range exceeded
Blinks every
1 sec
Notes
(1) If the module is normal, RDY LED is On.
(2) If 2 or more errors occur, the module will save the first error code generated, and the displayed error will be first
deleted to let the next error deleted.
(3) In case of serious error which makes RDY LED blinks every 0.2 sec., let power OFF -> ON to delete the error.
(4) In case of slight error which makes RDY LED blinks every 1 sec., the error can be deleted without power OFF ->
ON and the module can keep operating.
(5) In case of slight error which makes RDY LED blinks every 1 sec, the parameter value causing the applicable error
is not set on the module, with the existing parameter value kept as it is.