Chapter 6 Global Constant and Global Variable
6-2
2. Setting area of comparison output status
Channel 0
Channel 1
Constant
value
Contents Data setting range
_Fxy_PLCSTOP_OUT_EN 50
When XGI CPU module is STOP mode, comparison output
status (channel 0, channel 1 common)
0 or 1
3. Output area of the error code
Channel 0
Channel 1
Constant
value
Contents Data setting range
_Fxy_ERR_CODE 51 Error code (channel 0, channel 1 common) GET_###
6.1.2 The Configuration and Contents of Data
1. Count types (channel 0:
_Fxy_CH0_CNT_MODE, channel 1: _Fxy_CH1_CNT_MODE)
Setting value Contents
0 Linear count
1 Ring count
2. Pulse input types (channel 0: _Fxy_CH0_PLS_MODE, channel 1: _Fxy_CH1_PLS_MODE)
Setting value Contents
0 2 phase 1 multiplier
1 2 phase 2 multiplier
2 2 phase 4 multiplier
3 CW/CCW
4 1 phase /1 input /1 multiplier
5 1 phase /1 input /2 multiplier
6 1 phase /2 input /1 multiplier
7 1 phase /2 input /2 multiplier
3. Comparison output types (channel 0: _Fxy_CH0_CP_MODE, channel 1: _Fxy_CH1_CP_MODE)
Setting value Contents
0 In case of current count value < comparison reference value, OUT is On
1 In case of current count value comparison reference value, OUT is On
2 In case of current count value = comparison reference value, OUT is On
3 In case of current count value comparison reference value, OUT is On
4 In case of current count value > comparison reference value, OUT is On
5
In case of comparison minimum value
current count
value
comparison maximum value, OUT is On
6
In case of comparison minimum value
current count
value,
current count
value
comparison maximum value, OUT is On
Here, means 0 or 1.
4. Additional function types (channel 0: _Fxy_CH0_AUX_MODE, channel 1: _Fxy_CH1_AUX_MODE)
Setting value Contents
0 Not used
1 Count clear
2 Count latch
3 Sampling count
4 Input frequency measure
5 Revolution measure per unit time
6 Count disable

Table of Contents