Chapter 2 Specifications
2-16
2.4.4 Compared output
(1) High Speed counter module has a compared output function used to compare present count value with compared value in size to
output as compared.
(2) Available compared outputs are 2 for 1 channel, which can be used separately.
(3) Compared output conditions are 7 associated with <, ≤, =, ≥, >, ≤ ≤, ≥ ≥
(4) In order to make actual comparison enabled after compared output condition set, the compared enable signal is to be On, at this
time, output is displayed only on program (U device or Global variable), and in order to send out the actual external output with
LED turned On, the output enable signal is to be On.
1. Preset value < Compared value
If counted present value is less than compared value, output is sent out, and if present value increases to be equal to or greater
than compared value, output is not sent out.
Notes
(1) Compared result can be checked at U device for XGK, Global variable for XGI/XGR
(2) Compared output is a signal to be output at external terminal (33, 34, 35, 36).
2. Count value ≤ Compared value
If present count value is less than or equal to compared value, output is sent out, and if count value increases to be greater than
compared value, output is not sent out.