Specifications of High Speed counter module’s basic performance, preset/gate input and transistor output are as described below.
2.2.1 Performance specifications
Specification
Item
XGF-H02A XGF-HD2A
Signal A-phase, B-phase
Input type Voltage input (Open Collector) Differential input (Line Drive):
Count
Input signal
Signal level DC 5/12/24V
RS-422A Line Drive
/HTL LEVEL Line Drive
Maximum coefficient speed 200kpps 500kpps (HTL input is 250kpps)
Number of channels 2
Coefficient range Signed 32-bit (-2,147,483,648 ~ 2,147,483,647)
Linear Count (if 32-bit range exceeded, Carry/Borrow occurs,
the maximum/minimum count value displayed)
Count mode
(program setting)
Ring Count (repeated count within setting range)
1-phase input
2-phase input
Input mode
(program setting)
CW/CCW input
Increasing/decreasing operation setting by B-phase input
1-phase input
Increasing/decreasing operation setting by program
2-phase input Automatic setting by difference in phase
A-phase input: increasing operation
Up/down
Setting
CW/CCW
B-phase input: decreasing operation
1-phase input 1/2 multiplication (program setting)
2-phase input 1/2/4 multiplication (program setting)
Multiplicatio
n function
CW/CCW 1-multiplication
Signal Preset instruction input, auxiliary mode instruction input
Signal level DC 5V/12V/24V (by terminal selection) input type
Control
input
Signal type Voltage
Output points 2-point/channel (for each channel): terminal output available
Type
Select single-compared (>, >=, =, =<, <) or section compared output (included or excluded)
(program setting)
External
output
Output type Open collector output (Sink)
Notes
In XGR system, you can use HSC module only at extension base. You can’t equip HSC module at basic base.