Sequence of Operation Details
AuxC_Out (AV48)
Or
AuxE_Out (AV50)
PidHtg (%)
Var1(AuxC_Out
or AuxE_Out)
30%
100
AuxC_Formula (MSV14) != 4 An
alog
Or
AuxE_Formula (MSV41) != 4 Analog
100%
0
AuxC_Type or AuxE_Type
Parallel Fan (7)
AuxC_Out (AV48)
Or
AuxE_Out (AV50)
> 0%
AuxC_Formula (MSV14) == 4 On/Off
Or
A
uxE_Formula (MSV41) == 4 On/Off
TzControlMode (MSV34):
Tzone1.
PidRoomT_Htg
Tzone2.
PidRoomTz2_Htg
Average.
(PidRoomT_Htg + PidRoomTz2_Htg) / 2.0
Maximum Htg
MIN(PidRoomT_Htg, PidRoomTz2_Htg)
Maximum Clg
MAX(PidRoomT_Htg, PidRoomTz2_Htg)
3x Tzone.
TzControlMode (MSV34):
Tzone1.
PidRoomT_Htg
Tzone2.
PidRoomTz2_Htg
Tzone3.
PidRoomTz3_Htg
Average.
(PidRoomT_Htg + PidRoomTz2_Htg + PidRoomTz3_Htg) / 3.0
Maximum Htg
MIN(PidRoomT_Htg, PidRoomTz2_Htg, PidRoomTz3_Htg)
Maximum Clg
MAX(PidRoomT_Htg, PidRoomTz2_Htg, PidRoomTz3_Htg)
PidHtg (%)
Occupied
Additional Sequence of Operation Details in notes on page 13 for non-condensate avoidance
PidHtg (%) RoomT_Loc
(MSV17): 1x Tzone.
PidRoomT_Htg
2x Tzone.