Multi-State Values
Object
Instance
FCU
Object name
Description
Tags
Default value State texts
MSV12
AuxC_Loc Auxiliary output C physical location
Cfg
BO-2
None
AO-1
AO-2
BO-1
BO-2
BO-3
BO-4
Float BO-1,2
MSV13
AuxC_Type Auxiliary output C control type Cfg Elect. Bboard
None
Elect. Reheat
Water Reheat
Elect. Bboard
Water Bboard
DX Cool
Water Cool
Parallel Fan
Series Fan
MSV14
AuxC_Formula Auxiliary output C formula Cfg Pulse, Dir.
0-10 VDC, Dir.
0-10 VDC, Rev.
2-10 VDC, Dir.
2-10 VDC, Rev
On-Off
Pulse, Dir.
Pulse, Rev.
Please note that objects tagged as:
Cfg: represent configuration properties of the device that are typically only set once during commissioning and start-up
User: represent properties or objects that are typically manipulated by users of the controller
Status: represent objects or properties that are ‘’typically’’ meant to be displayed on graphics for various required visualization
Cmd: represent objects that can be controlled directly by other BACnet external process