■ ANALOG OUTPUT AO
OUTPUT 1
ADDR.
OUTPUT 2
ADDR.
OUTPUT 3
ADDR.
OUTPUT 4
ADDR.
WORD PARAMETER
7009 7039 7069 7099 1 Analog output 1 thr. 4 - Measurand to be assigned
Refer to the table in the following page.
7010 7040 7070 7100 1 Analog output 1 thr. 4 - Zero adjustment
-500 to +500 : %/100
Factory setting : 0
7011 7041 7071 7101 1 Analog output 1 thr. 4 - Span adjustment
9 500 to 10 500 : %/100
Factory setting : 10 000
7012 7042 7072 7102 1 Analog output 1 thr. 4 - Linearization
0 : Proportional output (*)
1 : Linearized output using the calibration table
7013 7043 7073 7103 1 Analog output 1 thr. 4 - Input 0%
-1 500 to +14 000 : %/100
Factory setting : 0
7014 7044 7074 7104 1 Analog output 1 thr. 4 - Output 0%
160 to 5 600 : mA/100 (4 – 20 mA) or mV (1 – 5 V)
Factory setting : 400 (4 – 20 mA) or 1 000 (1 – 5 V)
7015 7045 7075 7105 1 Analog output 1 thr. 4 - Input 100%
-1 500 to +14 000 : %/100
Factory setting : 10 000
7016 7046 7076 7106 1 Analog output 1 thr. 4 - Output 100%
160 to 5 600 : mA/100 (4 – 20 mA) or mV (1 – 5 V)
Factory setting : 2 000 (4 – 20 mA) or 5 000 (1 – 5 V)
7017 7047 7077 7107 1 Analog output 1 thr. 4 - Calibration point 0 input
-1 500 to +14 000 : %/100
Factory setting : 0
7018 7048 7078 7108 1 Analog output 1 thr. 4 - Calibration point 0 output
160 to 5 600 : mA/100 (4 – 20 mA) or mV (1 – 5 V)
Factory setting : 400 (4 – 20 mA) or 1 000 (1 – 5 V)
7019 7049 7079 7109 1 Analog output 1 thr. 4 - Calibration point 1 input
-1 500 to +14 000 : %/100
Factory setting : 0
7020 7050 7080 7110 1 Analog output 1 thr. 4 - Calibration point 1 output
160 to 5 600 : mA/100 (4 – 20 mA) or mV (1 – 5 V)
Factory setting : 400 (4 – 20 mA) or 1 000 (1 – 5 V)
7021 7051 7081 7111 1 Analog output 1 thr. 4 - Calibration point 2 input
-1 500 to +14 000 : %/100
Factory setting : 0
7022 7052 7082 7112 1 Analog output 1 thr. 4 - Calibration point 2 output
160 to 5 600 : mA/100 (4 – 20 mA) or mV (1 – 5 V)
Factory setting : 400 (4 – 20 mA) or 1 000 (1 – 5 V)
7023 7053 7083 7113 1 Analog output 1 thr. 4 - Calibration point 3 input
-1 500 to +14 000 : %/100
Factory setting : 0
7024 7054 7084 7114 1 Analog output 1 thr. 4 - Calibration point 3 output
160 to 5 600 : mA/100 (4 – 20 mA) or mV (1 – 5 V)
Factory setting : 400 (4 – 20 mA) or 1 000 (1 – 5 V)
7025 7055 7085 7115 1 Analog output 1 thr. 4 - Calibration point 4 input
-1 500 to +14 000 : %/100
Factory setting : 0
7026 7056 7086 7116 1 Analog output 1 thr. 4 - Calibration point 4 output
160 to 5 600 : mA/100 (4 – 20 mA) or mV (1 – 5 V)
Factory setting : 400 (4 – 20 mA) or 1 000 (1 – 5 V)
7027 7057 7087 7117 1 Analog output 1 thr. 4 - Calibration point 5 input
-1 500 to +14 000 : %/100
Factory setting : 0
7028 7058 7088 7118 1 Analog output 1 thr. 4 - Calibration point 5 output
160 to 5 600 : mA/100 (4 – 20 mA) or mV (1 – 5 V)
Factory setting : 400 (4 – 20 mA) or 1 000 (1 – 5 V)