RECOVERY AND RECHARGING PROCEDURES
Do not purge refrigerant to the atmosphere. Capture
refrigerant using recovery equipment. Follow the
manufacturer’s recommendations.
CONNECTIONS
1. Suction side of the compressor through the
suction service valve.
2. Discharge side of the compressor through the
discharge service valve.
Manitowoc Ice assumes no responsibility for the
use of contaminated refrigerant. Damage
resulting from the use of contaminated refrigerant
is the sole responsibility of the servicing company.
Replace the liquid line drier before evacuating
and recharging. Use only a Manitowoc (O.E.M.)
liquid line filter drier to prevent voiding the
warranty.