Manitowoc NEO - Discharge Pressure Troubleshooting; High Discharge Pressure Causes Checklist

Manitowoc NEO
136 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76 Part Number STH042 3/14
Discharge Pressure High Checklist
Improper Installation
• Refer to “Installation/Visual Inspection Checklist”
on page 64.
Restricted Condenser Air Flow
• High inlet air temperature
• Condenser discharge air re-circulation
• Dirty condenser fins
• Defective fan cycling control
• Defective fan motor
Improper Refrigerant Charge
• Overcharged
• Non-condensable in system
• Wrong type of refrigerant
Other
• Non-Manitowoc components in system
• High side refrigerant lines/component restricted
(before mid-condenser)
Freeze Cycle Discharge Pressure Low Checklist
Improper Installation
• Refer to “Installation/Visual Inspection Checklist”
on page 64.
Improper Refrigerant Charge
• Undercharged
• Wrong type of refrigerant
Other
• Non-Manitowoc components in system
• High side refrigerant lines/component restricted
(before mid-condenser)
• Defective fan cycle control
NOTE: Do not limit your diagnosis to only the items
listed in the checklists.