SECTION 6 – GRAPHICAL USER INTERFACE
The DVR
®
2000E+ Graphical User Interface (GUI) offers the user a means of programming the regulator and
monitoring generator performance. This Windows® based software is available as a free download from the
Marathon Electric website, www.marathonelectric.com. With this software, the user will be able to change all of
the user programmable parameters.
The GUI consists of a header, and three tabbed panels (Metering, Configuration and Identification). The
header displays regulator status and basic administration functions. The Metering tab displays metered quantities
and fault information. The Configuration tab permits regulator setting of all user programmable parameters. The
identification tab contains information specific to the regulator and allows for customer tags.
HEADER BUTTONS
Administration
This button allows the user to change serial port communication settings and modify passwords.
Login
The default user type is Customer. The type of user logged in is displayed in the header area.
Load Factory Settings
When this button is pressed, the default factory settings for the regulator are loaded into the regulator’s volatile
memory (Random Access Memory or RAM). These factory settings can be transferred to the user settings in non-
volatilememory(ElectricallyErasableProgrammableReadOnlyMemoryorEEPROM)bypressingthe“Saveto
EEPROM”button.
Save to EEPROM
When this button is pressed, all parameter values in the regulator’s RAM (Configuration and Identification tabs)
are transferred to the regulator’s user settings in EEPROM. These user settings are loaded into RAM whenever the
regulatorispoweredup.Anyparametersadjustedbeforesavingarelost.
Load Config
When this button is pressed, the user will be prompted to select a previously saved .xml file. When the file is
selected, all user-adjustable settings are loaded into the volatile RAM memory of the DVR®2000E+ from the
selected .xml file. These settings can be transferred to the user settings in non-volatile EEPROM by pressing the
“SavetoEEPROM”button.
Note: When a file is transferred from a computer to the regulator, the operating status will switch to “OFF” and
excitation be disabled To enable excitation, go to the Operating Modes sub panel of the Configure tab and click
the “Excitation ON” button.