PRELIMINARY SETUP – ON GENERATOR
: Use caution when working around the component side of the DVR
®
2000E+. Voltage levels
may be present at the exposed components when the unit is energized. The protective cover must be
installed whenever the regulator is energized.
: Read and understand the operation of the individual adjustments before attempting any
initial adjustments.
The regulator may be configured on the generator using the following procedure:
1. Before starting the engine, remove the regulator’s 4.0 A fuse. This will prevent the generator’s PMG from
energizing the regulator and prevent unintended operating functions from occurring.
2.Performallpreliminaryenginegovernoradjustmentswiththeregulatorde-energized.
3.Afterinitialgovernoradjustments arecomplete,shut down theprimemover.Reinstallthe4.0Afuse.
Disconnect the E3 and F+ terminal connectors from the regulator and temporarily insulate them to
prevent accidental shorting.
4. Start and run the generator at rated speed. The regulator will enter a Loss of Sensing shutdown mode,
indicated by f011 on the display.
5.At this time, initial adjustments can be made. If adjusting via the HMI, see “MAKING SETTINGS
CHANGES”inSection5.IfadjustingviatheWindowsCommunicationSoftware,seeSection6.
6.After the initial adjustments are made, shut down the generator and reconnect the regulator leads
removed in Step 3. The generator may be started and nal adjustments may be performed on the
regulator.