Mass Combi Ultra 12/3000-150, 24/3500-100, 48/3500-50 User and Installation Manual
29
Mass Combi Ultra
12/3000-150
24/3500-100
48/3500-50
Paralleling/3-phase
Parallel stacking
Yes, up to 10 standard from hardware version D
3-phase configuration
Yes, up to 3 x 3 from hardware version D
Solar charge regulator*
Max. solar voltage input
50 V
100 V
n/a
Start-up voltage
25 V
25 V
n/a
Max. solar panel (PV peak) power
500 Wp
500 Wp
n/a
Max. input current
19 A
19 A
n/a
Max. solar charge current
30 A @ 14.25 V
15 A @ 28.5 V
n/a
MPP Range
25 50 V
35 80 V
n/a
Recommended PV module
configuration
When you connect PV modules in
series and/or parallel, always use
PV modules of the same type and
specifications.
2x 36 cells in series
1x 72 cells
1x 60 cells
2 x 36 cells in series*
1 x 72 cells*
3 x 36 cells in series
4 x 36 cells in series
2 x 72 cells in series
2 x 60 cells in series
* possible but not
recommended, lower
energy production
n/a
General specifications
Dimensions (HxWxD)
472x318x178 mm
472x318x178 mm
472x318x178 mm
Weight
15.3 kg
15.3 kg
15.3 kg
Protection degree
IP23 (vertical wall mounting)
Safety class
IEC protection class I
Grounding
Ground relay standard, includes ground stud (ABYC compliant) configurable
Operating temperature
-25 ˚C to 60 ˚C, above 40 ˚C derating
Overvoltage category
Gen: OVII; Mains: OVIII
Pollution degree
PDII
Relative humidity
Protected against humidity and condensing air by conformal coating, max 95% relative
humidity, none condensing
Standards, approvals & listings
CE, ABYC
Options & features
Front panel display
Yes, shows charge state, inverter power, input/output state and includes on/off/inverter
off switch
Battery temperature sensor
Yes
Cooling
Maintenance free vario fans
MasterBus functionality
MasterBus powering
Standard on, selectable
Overload protection
Gen & Mains input
Digital fuse
Adjustable with three preset values
Frequency monitoring
Relay disconnects when frequency is out of range
Voltage monitoring
Relay disconnects when voltage is out of range
Overvoltage protection
Non recoverable protection of the unit
Output-1 & 2
Short circuit protection
Yes (inverter only)
Overload protection
Yes
Over temperature protection
Yes
AC backfeed protection
Yes
Main & Secondary battery
Short circuit protection
Yes
Reversed polarity protection
No
High / low battery voltage
Yes
* From hardware version E onwards, models 12/3000-150 and 24/3500-100 only