CD 30 ÷ 520
20
unit will calculate¥2 =Ts-45ˈthen adjust the capacity output according T˄T=44ˈ45ˈ46ˈ
47ˈ48ć˅+¥2 (T means the real temperature of total outlet water). The detail of heating
capacity adjustment is as following chart:
For example˖If the system have 11 sets of units, when T reduce to 45ć in HEATING mode,
the system will operate on 80%. So the actual operation units are 9 sets. (11*80%=8.8,adopts
9), and the main unit will stop two units which address is highest.
(2) Capacity adjustment of every one unit
Heating capacity adjustment
Temperature of heat exchanger
Cooling adjustment capacity in ON/OFF mode
Temperature of plate heat exchanger
Heating adjustment capacity in ON/OFF mode