EasyManuals Logo

McQuay IM 743 User Manual

McQuay IM 743
136 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #57 background imageLoading...
Page #57 background image
OM 780-2 Page 57
Number of Tower
Stages
This input sets the highest tower stage that the CSM will enable. It is typically set to the highest Stage # row with a Tower
Output set to On in the Tower Stage Table. Range = 1 to 12. Default = 6
Tower Stage
Differential
The cooling tower will not be staged down until the Control Temperature is less that the current Stage Setpoint minus this Tower
Stage Differential. Range = 0 – 9.5°F (0 – 5.2°C). Default = 3°F (1.7°C)
Tower Stage-Up
Delay Time
After a tower stage-up occurs, the next stage-up cannot occur until after this period of time expires. Range = 1 to 60 minutes.
Default = 2 minutes
Tower Stage-Down
Delay Time
After a tower stage-down occurs, the next stage-down cannot occur until after this period of time expires. Range = 1 to 60
minutes. Default = 5 minutes
Stage 1 to 12
Setpoints
Enter the temperature setpoints (up to 12) which correspond to the Stage # in the Tower Stage Table. When the control
temperature is higher than the setpoint the CSM will stage-up to enable more cooling tower capacity. These inputs also define
the differentials that will be maintained between each stage if the Stage 1 Setpoint is being reset. Range = 40-99.5°F (4.4 to
37.4°C). Defaults; Stage 1 Setpoint =74°F (23.3°C), 2=76°F (24.4°C), 3 through 12=78°F (25.5°C)
Tower VFD
Control Flag
This input allows CSM’s control of the cooling tower VFD to be turned on and off. If this flag = No, the CSM’s tower VFD
analog outputs will not modulate to maintain the control temperature. Default = No
Tower VFD
Deadband
This input sets a Deadband around the Stage 1 Setpoint if tower VFD control is used. No tower VFD control action is taken
when the current Control Temperature is within this Deadband around the Stage 1 Setpoint. Range = 0.5 – 10°F (0.2 – 5.6°C).
Default = 1.5°F (0.8°C)
Tower VFD
Propband
This value sets the “proportional band” used in the PID control function that modulates the tower VFD speed. In general,
increasing this value has a slowing effect and decreasing this value has a speeding effect on the control of the VFD speed.
Range = 1 – 60°F (0.5 – 33.3°C). Default = ±30°F (±16.7°C)
Tower VFD
Sample Time
This value sets the “sampling period” used in the PID control function that modulates the tower VFD speed. In general,
increasing this value has a slowing effect and decreasing this value has a speeding effect on the control of the VFD speed.
Range = 1 – 3600 seconds. Default = 15 seconds
Tower VFD
Integral Time
This value varies the “integral time” used in the PID control function that modulates the tower VFD speed. In general,
increasing this value has a slowing effect and decreasing this value has a speeding effect on the control of the VFD speed.
Range = none. Default = 120 seconds
Tower VFD PI
Function Graph
A graph of the tower Control Temperature vs. Time is shown at the bottom of the page when the Tower VFD Control Flag = Yes
to assist in tuning the Tower VFD PI loop.
Tower VFD
Minimum Speed
This input sets the minimum percentage from the CSM’s tower VFD analog output. Range = 25 – 99 %. Default = 45%
Fan Speed of the
First Non-VFD Fan
When VFD’s are used on some (but not all) cooling tower fans and the non-VFD fans have multi-speed control, set this input to
the lowest multiple fan speed. Then place all VFD controlled fans in Stage 1, and place the lowest fan speed in Stage 2. Stage 2
will only be enabled after the VFD controlled fans reach the Fan Speed of the First Non-VFD Fan. Range = 33 – 100 %.
Default = 100%
Constant Approach
Reset Flag
This input allows Stage 1 Setpoint reset based on the outside air wet-bulb temperature to be turned on and off. If this flag = Yes,
the CSM’s cooling tower stage setpoints will change to maintain a constant temperature differential between the common
entering condenser water and the ambient wet-bulb. Relative humidity and outside air temp sensors are required. Default = Off
Constant Approach
Temperature
Differential
This input sets the constant temperature differential that will be added to the wet-bulb temperature to reset the CSM’s cooling
tower Stage 1 Setpoint (if Constant Approach Reset Flag = Yes). Note that all of the other Stage Setpoints (2 through 12) are
also reset to maintain their original user defined differentials from the Stage 1 Setpoint. Range = 5-25 °F (2.8 - 13.9°C). Default
= 7°F (3.9°C)
Constant Approach
Reset – Minimum
Setpoint
This input sets the minimum value for the cooling towers Stage 1 Setpoint when using Constant Approach Reset. Resetting the
condenser entering water too low during cold weather could cause chiller operating problems. Range = 40 – 99.5°F (4.4 –
37.5°C). Default = 74°F (23.3°C)
Cooling Tower Bypass Valve
Name Description
Tower Valve
Control Option
This input tells the CSM if there is a cooling tower bypass valve. If there is a valve, you further define what setpoint the valve will
use. Range = None, Valve Setpoint, Stage Setpoint. Default = None
Tower Valve
Setpoint
This input is the user defined cooling tower valve setpoint. If the Tower Valve Control Option = Valve Setpoint, the valve will be
modulated to maintain the Control Temperature at this setpoint. Range = 40 – 99.5°F (4.5 – 37.5°C). Default = 70°F (21.1°C)
Tower Valve
Control Range
Min
This input defines the lowest valve position the CSM will send to the tower bypass valve. Range = 0 – 100%. Default = 0%
Tower Valve
Control Range
Max
This input defines the highest valve position the CSM will send to the tower bypass valve. Range = 0 – 100%. Default = 100%
Min Tower Valve
Position Setpoint
This value is used as a stage-down condition for interstage control when the Tower Valve Control Option = Stage Setpoint. Range
= Tower Valve Control Range Min – 100%. Default = 20%

Table of Contents

Other manuals for McQuay IM 743

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay IM 743 and is the answer not in the manual?

McQuay IM 743 Specifications

General IconGeneral
BrandMcQuay
ModelIM 743
CategoryController
LanguageEnglish

Related product manuals