Operation Manual
OM 780-2
Group: Controls
Part Number: OM 780-2
Date: November 2005
Supersedes: OM 780-1
MicroTech II
Chiller System Manager (CSM) Operation Manual
For
MicroTech II Chillers
Hardwired Chillers

Table of Contents

Other manuals for McQuay MicroTech II

Questions and Answers

  • S
    sarahjosephAug 19, 2025
    Why can't I access the McQuay Controller CSM user interface?
    • T
      Tanner WiseAug 20, 2025
      If you cannot access the McQuay Controller CSM user interface despite having correct settings in your browser, it might be because the IP address of your computer is not set to be one number away from the IP address of the CSM. To resolve this, set the IP address of your computer to be one number away from the IP address of the CSM.
  • N
    Nicholas RiversAug 21, 2025
    What to do if the McQuay MicroTech II CSM user interface does not appear?
    • P
      Peter SimmonsAug 21, 2025
      If the McQuay Controller CSM user interface does not appear in your web browser even after successfully pinging the CSM, it's possible that your PC is configured to use a proxy server. To fix this, disable Internet Explorer’s use of a proxy server.
  • K
    Krystal ReillyAug 25, 2025
    How to connect my computer to McQuay MicroTech II CSM over Ethernet?
    • B
      Brett MartinezAug 25, 2025
      If you're having difficulty connecting your computer to the McQuay Controller CSM over an Ethernet connection, it could be because the computer’s IP address and subnet mask are not compatible with the CSM’s IP address and subnet mask. Make sure that the subnet masks are exactly the same on both devices and that the IP addresses are close enough to be on the same subnet.
  • W
    warrenrichardAug 26, 2025
    What to do if McQuay Controller unit does not leave Fan Only and enter Heating operating state?
    • M
      Maria GordonAug 26, 2025
      If your McQuay Controller unit remains in Fan Only mode and doesn't switch to Heating, check the Htg Status= parameter in the System menu to ensure it indicates “Htg Ena.” Also, the current value of the Ctrl Temp= parameter must be below the Eff Htg Spt= by more than half the Htg Deadband= parameter in the Zone Heating menu. If the Ctrl Temp= is not below the Eff Htg Spt= by more than half the Htg Deadband= parameter in the Zone Heating menu, the Eff Htg Spt= parameter must be adjusted accordingly to enable heating operation. If the unit still does not enter the Heating operating state, the MCB is likely defective.
  • J
    Joel BatesAug 29, 2025
    What to do if McQuay MicroTech II Controller unit does not leave the Off Alm operating state?
    • M
      Melissa BarryAug 30, 2025
      If your McQuay Controller unit remains in the Off Alm operating state, first check the Active Alarm 1 menu for any active “faults.” The alarm condition must be corrected and the “fault” cleared before the unit can be started. If the Active Alarm 1 menu indicates “None” or an alarm type other than a “fault” and the UnitStatus= parameter in the System menu continues to indicate “Off Alm”, the MCB is likely defective.
  • R
    Robert RobersonSep 2, 2025
    What to do if McQuay Controller unit does not leave the Off Man operating state?
    • D
      Dr. Rachel HigginsSep 3, 2025
      If your McQuay Controller unit remains in the Off Man operating state, check the Ctrl Mode= parameter in the System menu. If it is set to “Off”, the UnitStatus= parameter indicates “Off Man.” If the Ctrl Mode= parameter in System menu is set to anything other than “Off” and the UnitStatus= parameter in the System menu still indicates “Off Man.”, the MCB is likely defective.
  • C
    carolyn02Sep 5, 2025
    What to do if McQuay MicroTech II Controller unit does not leave the Off Sw operating state?
    • J
      Jenny BridgesSep 5, 2025
      If your McQuay Controller unit remains in the Off Sw operating state, and terminal 101 is not made to 104 on TB2 (binary input MCB-BI2 is off) and the UnitStatus= parameter continues to indicated “Off Sw”, the MCB is likely defective.
  • R
    Ryan HunterSep 7, 2025
    What to do if the McQuay MicroTech II Controller MCB is suspected to be defective?
    • A
      Anthony HaneySep 7, 2025
      If you suspect the McQuay Controller MCB is defective, perform a 'cold' reboot by removing the MCB battery and cycling power to the controller.
  • A
    Amber GentrySep 8, 2025
    What to do if I get a battery warning on my McQuay MicroTech II?
    • B
      Brent SnowSep 9, 2025
      If you receive a battery warning on your McQuay Controller, it means the battery is reaching the end of its useful life and should be replaced within 14 days.
  • R
    robert30Sep 12, 2025
    What to do if Error LED remains on after battery replacement in McQuay MicroTech II Controller?
    • R
      Rachel TorresSep 12, 2025
      To address this issue, cycle power to the MCB. Also, note that the battery is tested at two minutes after midnight each day. Alternatively, issue a battery test command with a PC using the MicroTech II Service Tool.

Summary

Getting Started with CSM

Connecting to the CSM

Establishes the initial network link between PC and CSM.

Connecting Your PC to the CSM

Provides steps to establish the initial PC to CSM connection.

Changing CSM IP Address and Date;Time

Configures network identity and system time settings for the CSM.

Accessing the CSM User Interface

Describes how to access the CSM via its web-based interface.

Password Protection and User Accounts

Configuring User Accounts

Manages user access levels and permissions for the CSM interface.

Connecting Chillers and Remote I;O

Commissioning LONWORKS Devices

Adds and configures network devices like chillers and I/O modules.

Commissioning a Chiller to CSM

Assigns chillers to specific CSM numbers for network management.

Commissioning Remote I;O Modules

Adds remote I/O modules to the CSM for expanded capabilities.

Setting up CSM Chiller Data

Configures specific data for each connected chiller for proper operation.

Communication Loss Control

Receive Heartbeat Settings

Sets the time limit before communication loss is detected by the chiller.

Setting Up CSMs I;O Configuration

Chiller Unit Controller Settings

Configuring the Chiller System Manager

System Control Overview

Manages overall CSM operating states and critical parameters.

CSM Control Mode Configuration

Sets the primary operating mode (Occupied, Unoccupied, Automatic).

Chiller Sequencing Control

Sequencing and Staging Explained

Defines how chillers are enabled/disabled to match cooling load.

Sequence Order Configuration

Sets the priority for enabling and disabling chillers in the system.

Standard Sequencing Logic

Decoupled Sequencing Logic

Load Limiting Control

Demand Limiting Configuration

Restricts system electrical demand to a set percentage.

Chilled Water Temperature Control

Chilled Water Supply Temperature Control

Sets the target supply water temperature for the system.

Chilled Water Supply Temperature Reset

Adjusts supply temperature based on load or other factors.

System Setpoint Management

Defines the primary system temperature setpoint.

Setpoint Reset Configuration

Configures automatic adjustment of system setpoints for efficiency.

Constant Return Chilled Water Temperature Control

Tower Staging Logic

Tower Bypass Valve Control

Chilled Water Flow Control

Load Flow Control Configuration

Configures pump logic and flow control for the chilled water system.

Sequencing Constant Flow Pumps

Manages multiple pumps operating in sequence for flow control.

Pump Logic: Lead;Standby

Pump Logic: Sequenced Constant-Speed Pumps

Pump Speed Control

Scheduling CSM Operation

Optimal Start Feature

BAS Communication Setup

Alarm Notification Methods

E-Mail Alarm Notification Setup

Sets up email alerts for alarm conditions.

Operators Guide to CSM

Chiller System Status Overview

Provides an overview of the chiller system's operational state.

CSM Operating State Details

Indicates the current overall operating mode of the CSM system.

Monitoring Chiller Status

Chiller Run Mode Status

Displays the current operational state of individual chillers.

Alarm Monitoring and Control

Acknowledging Alarms on CSM

Process for acknowledging and clearing system alarms.

Clearing CSM Alarms

Steps to clear manual-reset alarms from the CSM.

CSM Alarms and System Control

Categorizes alarms and their impact on system operation.

No Chilled Water Flow Alarm

Problem Alarms

Troubleshooting CSM Issues

Troubleshooting PC Connection to CSM

Guides on resolving issues connecting PC to the CSM.

Checking PC IP Address and Subnet Mask

Verifies PC network settings for compatibility.

Determining CSM IP Address and Subnet Mask

Finds the CSM's network configuration details.

Hardwired Chiller Alarms

McQuay MicroTech II Specifications

General IconGeneral
BrandMcQuay
ModelMicroTech II
CategoryController
LanguageEnglish