OM 780-2 Page 51
Figure 17. CSM Leaving Evaporator Water Temperature Setpoint Flow Chart
Notes:
1. When the Chilled Water Temperature Reset Type is “None,” the System Setpoint can be set manually.
Return ChWT Spt
External Signal
External Reset
Max System Spt
Outdoor Air Temp
OAT Reset
Max Sys Spt At
Min Sys Spt At
Max System Spt
Return Water
Temperature
Return Reset
Max Sys Spt At
Min Sys Spt At
Max System Spt
Min System Spt
RChWT
OAT
External
Constant RChWT
None
Reset Type
Reset Override
System Setpoint
Supply Water
Temperature (PA)
Min Chiller Spt
Unit
Common
Control Option
Chiller Setpoint
Max System Spt
Reset Ovr.
Common Supply
PI Function
See note 1
Return Water
Temperature (PA)
Constant Return
PI Function
a0145
Operator System Setpoint