Model : M5ACV 030 / 055CR - Heating
66
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A kW kW A m3/hr kPa W A
35 3.82 3.77 14.4 5.04 3.80 14.5 7.82 3.83 14.7 1.89 57 227 1.0
40 2.71 4.02 15.4 4.08 4.05 15.5 7.11 4.11 15.7 1.80 61 222 1.0
45 1.61 4.42 16.9 3.03 4.45 17.0 6.20 4.50 17.2 1.66 70 215 0.9
50 0.66 4.67 17.9 2.00 4.70 18.0 5.02 4.77 18.3 1.44 77 204 0.9
55 0.31 4.99 19.1 1.27 5.03 19.2 3.56 5.10 19.5 1.12 93 186 0.8
35 12.55 4.71 10.8 13.51 4.84 11.1 15.11 5.06 11.6 2.74 114 272 1.2
40 12.12 5.09 11.7 12.87 5.18 11.9 14.57 5.32 12.2 2.71 116 270 1.2
45 11.73 5.35 12.3 12.47 5.51 12.6 14.16 5.80 13.3 2.64 120 266 1.2
50 10.05 5.75 13.2 10.78 5.85 13.4 12.45 6.02 13.8 2.35 137 251 1.1
55 7.08 6.13 14.0 7.80 6.19 14.2 9.45 6.31 14.4 1.83 161 224 1.0
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A kW kW A m3/hr kPa W A
35 9.74 3.84 14.7 11.00 3.83 18.3 12.11 3.81 14.6 1.89 57 227 1.0
40 9.15 4.14 15.8 10.44 4.14 19.7 11.54 4.14 15.8 1.80 61 222 1.0
45 8.32 4.45 17.0 9.67 4.51 21.5 10.82 4.50 17.2 1.66 70 215 0.9
50 7.07 4.80 18.4 8.39 4.81 22.9 9.54 4.80 18.4 1.44 77 204 0.9
55 5.28 5.12 19.6 6.50 5.13 24.4 7.66 5.12 19.6 1.12 93 186 0.8
35 15.94 5.10 11.7 16.77 5.07 11.9 17.41 4.98 11.4 2.74 114 272 1.2
40 15.74 5.34 12.2 16.50 5.31 12.5 17.17 5.25 12.0 2.71 116 270 1.2
45 15.34 5.86 13.4 16.12 5.85 13.7 16.82 5.74 13.1 2.64 120 266 1.2
50 13.63 6.05 13.9 14.43 6.03 14.2 15.15 5.97 13.7 2.35 137 251 1.1
55 10.63 6.33 14.5 11.43 6.32 14.8 12.15 6.28 14.4 1.83 161 224 1.0
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A m3/hr kPa W A
35 13.63 3.76 14.4 14.90 3.67 14.1 1.89 57 227 1.0
40 12.93 4.10 15.7 13.88 4.03 15.4 1.80 61 222 1.0
45 12.27 4.45 17.0 13.27 4.37 16.7 1.66 70 215 0.9
50 11.56 4.77 18.2 12.19 4.70 18.0 1.44 77 204 0.9
55 9.46 5.07 19.4 11.40 4.99 19.1 1.12 93 186 0.8
35 18.27 4.70 10.8 19.14 4.15 9.5 2.74 114 272 1.2
40 18.07 5.05 11.6 18.79 4.66 10.7 2.71 116 270 1.2
45 17.79 5.42 12.4 18.65 4.80 11.0 2.64 120 266 1.2
50 16.17 5.77 13.2 17.11 5.36 12.3 2.35 137 251 1.1
55 13.20 6.15 14.1 14.17 5.89 13.5 1.83 161 224 1.0
M5ACV055CR
LEAVING WATER TEMP (°C
)
LEAVING WATER TEMP (°C
)
AMBIENT TEMPERATURE ON CONDENSOR (°C)
AMBIENT TEMPERATURE ON CONDENSOR (°C)
AMBIENT TEMPERATURE ON CONDENSOR (°C)
LEAVING WATER TEMP (°C)
-7 -5 0
4710
15 21
M5ACV030CR
MODEL
M5ACV030CR
MODEL
M5ACV030CR
MODEL
M5ACV055CR
M5ACV055CR

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the McQuay M5ACV 030 CR and is the answer not in the manual?

McQuay M5ACV 030 CR Specifications

General IconGeneral
BrandMcQuay
ModelM5ACV 030 CR
CategoryChiller
LanguageEnglish

Related product manuals