Model : M5ACV 075CR - Heating
67
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A kW kW A m3/hr kPa W A
35 14.25 6.87 13.4 16.02 6.92 13.5 19.83 7.06 13.8 4.00 183 748 1.4
40 12.74 7.43 14.5 14.68 7.47 14.6 18.82 7.59 14.8 3.87 191 749 1.4
45 11.32 8.02 15.6 13.36 8.05 15.7 17.70 8.17 15.9 3.71 201 750 1.4
50 10.00 8.64 16.8 12.06 8.66 16.9 16.45 8.80 17.2 3.50 214 751 1.3
55 8.75 9.30 18.1 10.77 9.32 18.2 15.08 9.48 18.5 3.26 228 752 1.3
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A kW kW A m3/hr kPa W A
35 22.24 7.24 14.1 23.68 6.78 13.2 24.80 6.83 13.3 4.00 183 748 1.4
40 21.42 7.78 15.2 22.95 7.31 14.3 24.11 7.38 14.4 3.87 191 749 1.4
45 20.40 8.36 16.3 21.98 7.90 15.4 23.17 7.95 15.5 3.71 201 750 1.4
50 19.18 8.98 17.5 20.78 8.55 16.7 21.98 8.60 16.8 3.50 214 751 1.3
55 17.76 9.63 18.8 19.34 9.26 18.1 20.53 9.28 18.1 3.26 228 752 1.3
WATER AVAIL. PUMP PUMP
HEAT POWER RUNNING HEAT POWER RUNNING FLOW HEAD INPUT INPUT
CAP. INPUT CURRENT CAP. INPUT CURRENT RATE PRESS. POWER AMP
kW kW A kW kW A m3/hr kPa W A
35 25.44 6.50 12.7 26.18 5.93 11.6 4.00 183 748 1.4
40 24.75 7.07 13.8 25.31 6.54 12.8 3.87 191 749 1.4
45 23.83 7.60 14.8 24.27 7.15 13.9 3.71 201 750 1.4
50 22.65 8.29 16.2 23.05 7.75 15.1 3.50 214 751 1.3
55 21.24 8.94 17.4 21.66 8.34 16.3 3.26 228 752 1.3
M5ACV075CR
MODEL
M5ACV075CR
MODEL
M5ACV075CR
MODEL
710
15 21
LEAVING WATER TEMP (°C