OM Centrif Micro ΙΙ-5 27
TIMERS Setpoint
Figure 15, TIMERS Setpoint Screen
Table 13, TIMER Setpoints
Description No. Default Range
Pass-
word
Comments
Postlube Timer 8 30 sec 10 to 240 sec T Time for postlube before compressor can stop
Unload Timer 7 30 sec 10 to 240 sec T Time compressor will unload before going to postlube
Full Load Timer 6 300 sec 0 to 999 sec T Time compressor must load for full open vanes
Interlock 5 WMC only
Prelube Timer 4 30 sec 10 to 240 sec T Time compressor must prelube before starting
Stop-Start 3 3 min 3 to 20 min M
Time from when compressor stops to when it can
restart
Start-Start 2 40 min 15 to 60 min M
Time from when compressor starts to when it can start
again
Evap
Recirculate
1 30 sec
15 sec to 5
min
M
Time that evaporator pump must run before
compressor start