DC32D GENSET CONTROLLER USER MANUAL
24
Delay
or low voltage.
16
Choke close delay
0-200.0s(3.0s)
Choke close delay.
17
Fuel output delay
1.0-60.0s(2.0s)
The output time of fuel valve relay before crank.
18
Pump fail warn
delay
06500.0s
(300.0s)
Detect the delay time from early warning to
alarm shutdown after the "pumping failure
alarm" switch is effective.
19
Back to Gens time
0-3600.0s(5.0s)
There shall be loading delay from Mains to
Gens if the remote start signal valid or Mains
abnormal under Cooling time.
20
Closing output time
1.0-10.0s(10.0s)
when it is 10s, it is regarded as continuous
output.
21
Opening output
time
0.0-10.0s(3.0s)
when it is 0s, it is regarded as disable unload
output.
22
Mains closing
delay
0-3600.0s(1.0s)
The delay time before the mains is closed.
23
Gens closing delay
0-3600.0s(3.0s)
The delay time before the generation is closed.
3)Engine Alarm setting
NO
Parameter
Range
(defaults)
Notes
1
Over speed
alarm
0-200%
(114%)
Rated RPM multiplying by this value is regarded as over
speed alarm value.When the RPM is higher than the
alarm value and comes into over speed delay but still
higher(emergency faults delay), then over speed
alarms. if the value is set as 200, then the over speed
alarm is disabled.
2
Under speed
alarm
0-200%
(80%)
Rated RPM multiplying by this value is regarded as
under speed alarm value.When the RPM is lower than
the alarm value and comes into under speed delay but
still lower (normal faults delay), then under speed
alarms. if the value is set as 0, then the under speed
alarm is disabled.
3
High
temperature
alarm
20-200
(98
)
When the temperature is higher than the alarm value
and comes into high temperature delay but still higher
(normal faults delay), then high temperature alarms. If
the value is set as 200, then the high temperature alarm
is disabled.
4
Low fuel level
warning
0-100%
(10%)
When the fuel level is lower than the value and comes
into low fuel level warning delay but still lower (normal
warning delay), then low fuel level warns. If it is higher
than the value then warning clears. If the value is set as
0, then the low fuel level warning is disabled.
5
Over battery
voltage
warning
0-200%
(135%)
Rated battery voltage multiplying by this value is
regarded as over battery voltage warning value.When
the battery input is higher than the warning value and
comes into over battery voltage delay but still higher
(normal faults delay), then over battery voltage warns.
if the value is set as 200, then the over battery voltage
is disabled.
6
Under battery
voltage warning
0-200%
(67%)
Rated battery voltage multiplying by this value is
regarded as under battery voltage warn value.When the