DC32D GENSET CONTROLLER USER MANUAL
23
regarded as crank success condition. When
the RPM is over the condition value, then
system regards it as crank success, motor
escaped.
16
Temperature for
Fan open
20200(75
)
Used for controlling radiator: when the
temperature reaches the set temperature, then
the radiator is opened.
17
Temperature for
Fan close
20200(60
)
Used for controlling radiator: when the
temperature is lower than the set temperature,
then the radiator is closed.
18
Maintenance
countdown
0-5000h(500h)
When it is set as 5000, then this function is
disabled.
19
Maintenance
expire
Warning/Alarm and
stop
The action after the primary maintenance
expired.
20
Maintenance
expiry reset
password
0-65535
06869
When the maintenance countdown time
arrives, enter the password to reset the
maintenance countdown time, this password
cannot be the same as the parameter setting
password.
21
User password
00000-65535(07623)
Change the password.
2)Delay time setting
NO
Parameter
Range(default)
Notes
1
Start delay
0-65000s(1s)
The time during the genset starts after the
remote start signal is valid.
2
Stop delay
0-6500.0s(1.0s)
The time during the genset stop after the remote
start signal is invalid.
3
Preheat time
0-6500.0s(0.0s)
The time needed to be preheat before the
starter on power.
4
Cranking time
3.0-60.0s(8.0s)
The time when the starter is on power.
5
Crank rest time
3.0-60.0s(10.0s)
If crank failure, the waiting time before the
second test time.
6
Safety delay
1.0-60.0s(10.0s)
Low oil pressure, high temperature, under
speed, under frequency, under voltage, are all
invalid during this time except for emergency
stop ,over speed, over freq.
7
Start idle time
0-3600.0s(0.0s)
Idle running time when crank successfully.
8
Warming-up time
0-3600.0s(10.0s)
The time needed for loading.
9
Cooling time
0-3600.0s(10.0s)
After unloading, the time of cooling down by
radiator before stop. During the delay, if the
remote start signal is valid, then genset will
come into rated running.
10
Stop idle time
0-3600.0s(0.0s)
Idle-speed running time.
11
E.T.S. hold time
0-600.0s(10.0s)
Stop solenoid on power time.
12
Fail to stop
5-180.0s(30.0s)
If the RPM is 0 during the stop failure time, then
the stop failure time is no needed.
13
Emergency delay
0-10.0s(1.5s)
Over Speed and over frequency emergency
alarm delay.
14
Normal alarm delay
2.0-20.0s(5.0s)
The alarm delay except for over speed
/emergency/over frequency.
15
Gens Abnormal
2.0-20.0s(10.0s)
It is used for alarm delay of generator with high